National Association of Testing Authorities, Australia
Scope of Accreditation
ENERGY QUEENSLAND LIMITED
Site
High Voltage Laboratory
Accreditation No.
74
Site No.
20788
Date of Accreditation
Contact
Availability
Services available to external clients
Scope of Accreditation
Withdrawn
ISO/IEC 17025 (2005)
Calibration
- The uncertainty of measurement is reported as an expanded uncertainty having a level of confidence of 95% unless stated otherwise
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Service | Product | Determinant | Technique | Procedure | Limitations | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
DC and low frequency electrical metrology - Electrical measurement and test equipment(Laboratory and on-site) | Voltmeters | AC voltage; DC voltage | Comparison with a reference standard | High voltage voltmeters | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Capability Including laboratory and on-site calibrationswith Calibration and Measurement Capability of - 2% from - 80 kV to -1 kV and +1 kV to +60 kV DC 2 % from 1 kV to 300 kV at 50 Hz AC |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
DC and low frequency electrical metrology - High-voltage/high-current standards and equipment(laboratory and on-site) | High voltage dividers; High voltage test sets | Voltage | Comparison with a reference standard | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Capability Including laboratory and on-site calibrations With Calibration and Measurement Capability of - High voltage test sets 2% from - 300 kV to -1 kV and +1 kV to +300 kV DC High voltage dividers 2% from - 80 kV to -1 kV and +1 kV to +600 kV DC |
ISO/IEC 17025 (2005)
Infrastructure and Asset Integrity
|
|||||
Service | Product | Determinant | Technique | Procedure | Limitations |
---|---|---|---|---|---|
Evaluation of high voltage/power equipment and components - Performance | Clothing materials, gloves and tools for use in high voltage/power applications | High voltage withstand; Leakage current; Visual examination | Dielectric tests with alternating or direct voltages |
AS 2225, ASTM D120, ASTM D1051, ASTM F496, ASTM F711, ASTM F1236 IEC 60855 and IEC 60903 |
Tests on gloves, sleeves, sticks, tubes, rods |
Insulated systems | High voltage withstand; Leakage current; Visual examination | Dielectric tests with alternating or direct voltages |
AS/NZS 2978, AS 4202, ASTM F478, ASTM D1048, ASTM D1050, ASTM D178, ASTM F479, ASTM F712, ASTM F2320 IEC 61111, IEC 61243-1 |
Tests on mats, drapes, sheeting, blankets, covers/guards, line cover/hoses, voltage detectors | |
Evaluation of high voltage/power equipment and components - Performance(Laboratory and on-site testing) | Platform access equipment for use in high voltage/power applications | Electrical continuity; High voltage withstand; Insulation resistance; Leakage current; Visual examination | Dielectric tests with alternating or direct voltages |
Laboratory and on-site testing AS/NZS 1418.10, AS 2550.1 Section 7 |
Including laboratory and on-site testing of Mobile Elevating Work Platforms (MEWPs) Laboratory periodic testing to 105 kV a.c.r.m.s On-site acceptance and periodic testing to 275 kV a.c.r.m.s |
The only data displayed is that deemed relevant and necessary for the clear description of the activities and services covered by the scope of accreditation.
Grey text appearing in a SoA is additional freetext providing further refinement or information on the data in the preceding line entry.
Accreditation No.
74
Site No.
20788
Print date
24 Jun 2022