Switchmode Power Supplies Pty Ltd

Site

Switchmode Power Supplies

Accreditation No.

16641

Site No.

17961

Date of Accreditation

24 Nov 2009

Address

1/37 Leighton Place
Hornsby , NSW 2077
Australia

switchmode.com.au

Contact

Mr Martin Griffith P: +61 (02) 94760300

Availability

Services available to external clients

Scope of Accreditation

Switchmode Power Supplies

ISO/IEC 17025 (2017)

Calibration

  • The uncertainty of measurement is reported as an expanded uncertainty having a level of confidence of 95% unless stated otherwise
Service Product Determinant Technique Procedure Limitations
DC and low frequency electrical metrology - Electrical measurement and test equipment Ammeters; Digital multimeters (DMM) AC current; DC current Direct measurement against a reference standard

Capability

with Calibration and Measurement Capability of -

D.C. ammeters

0.10% from 0.1 mA to < 1 mA
0.25% from 1 mA to < 10 mA
0.10% from 10 mA to < 1000 mA
0.01% + 0.4 mA from 1 A to < 20 A
0.12% from 20 A to < 100 A
0.22% from 100 A to 400 A

A.C. ammeters

0.16% + 0.04 mA from 10 mA to < 100 mA from 10 Hz to 5 kHz
0.16% + 0.4 mA from 100 mA to < 1000 mA from 10 Hz to 5 kHz
0.19% + 2.2 mA from 1 A to < 10 A from 10 Hz to 5 kHz
0.50% from 10 A to < 20A from 10 Hz to 5 kHz
 0.66% from 20 A to 100 A from 10 Hz to 400 Hz

Digital multimeters (DMM); Voltmeters AC voltage; DC voltage Direct measurement against a reference standard

Capability

with Calibration and Measurement Capability of -

D.C. voltmeters

10 µV from 1 mV to <100 mV                
0.011% from 0.1 V to 1000 V

A.C. voltmeters

0.52% from 10 mV to 1000V from 10 Hz to 20 Hz
0.06% + 0.03 mV from 10 mV to < 100 mV from 20 Hz to 20 kHz
0.06% + 0.3 mV from 100 mV to < 1000 mV from 20 Hz to 20 kHz
0.06% + 0.003 V from 1 V to < 10 V from 20 Hz to 20 kHz
0.06% + 0.03 V from 10 V to < 100 V from 20 Hz to 20 kHz
0.06% + 0.225 V from 100 V to 1000 V from 20 Hz to 20 kHz
0.032% at 100 V 45 Hz
0.024% at 135 V 60 Hz
0.024% at 135 V 400 Hz
0.027% at 135 V 5000 Hz
0.023% at 140 V 60 Hz
0.023% at 140 V 1150 Hz
0.015% at 250 V 60 Hz
0.020% at 250 V 1150 Hz
 0.014% at 270 V 400 Hz

Power supplies AC current; AC voltage; Active power; DC current; DC voltage Direct measurement against a reference standard

Capability

Power supplies and power conditioners
Power supply equipment and systems
with Calibration and Measurement Capability of -

D.C. voltage
10 µV from 1 mV to <100 mV
0.011% from 0.1 V to 1000 V

A.C. voltage
0.52% from 10 mV to 1000V from 10 Hz to 20 Hz
0.06% + 0.03 mV from 10 mV to <100 mV from 20 Hz to 20 kHz
0.06% + 0.3 mV from 100 mV to < 1000 mV from 20 Hz to 20 kHz
0.06% + 0.003 V from 1 V to < 10 V from 20 Hz to 20 kHz
0.06% + 0.03 V from 10 V to <100 V from 20 Hz to 20 kHz
0.06% + 0.225 V from 100V to 1000 V from 20 Hz to 20 kHz
0.032% at 100 V 45 Hz
0.024% at 135 V 60 Hz
0.024% at 135 V 400 Hz
0.027% at 135 V 5000 Hz
0.023% at 140 V 60 Hz
0.023% at 140 V 1150 Hz
0.015% at 250 V 60 Hz
0.020% at 250 V 1150 Hz
0.014% at 270  V 400 Hz

D.C. current
0.10% from 0.1 mA to < 1 mA
0.25% from 1 mA to <10 mA
0.10% from 10 mA to <1000 mA
0.01% + 0.4 mA from 1 A to <20 A
0.12% from 20 A to <100 A
0.22% from 100 A to 400 A

A.C. current 
0.16% + 0.04 mA from 10 mA to <100 mA from 10 Hz to 5 kHz
0.16% + 0.4 mA from 100 mA to <1000 mA from 10 Hz to 5 kHz
0.19% + 2.2 mA from 1A to <10 A from 10 Hz to 5 kHz
0.50% from 10A to < 20A from 10 Hz to 5 kHz
0.66% from 20 A to 100 A from 10 Hz to 400 Hz

DC power (Up to 50 kW)
0.10% from 1 V to 1000 V and 0.1 A to <1 A
0.05% from 1 V to 1000 V and 1 A to <20 A
0.12% from 1 V to 1000 V and 20 A to <100 A
 0.22% from 1 V to 1000 V and 100 A to 400
 
Active Power (Up to 50 kW, Unity Power Factor)
0.71% from 1 V to 1000 V and 0.1 A to <1 A and 10 Hz to 5 kHz                                                                      
0.60% from 1 V to 1000 V and 1 A to <10 A and 10 Hz to 5 kHz                                                                        
0.67% from 1 V to 1000 V and 10 A to <20 A and 10 Hz to 5 kHz                                                                      
0.80% from 1 V to 1000 V and 20 A to 100 A and 10 Hz to 400 Hz

Frequency                            
0.030% from 10 Hz to 300 kHz              
                             
Time interval                          
0.4 s from 1 s to 10000 s

Watt meters Active power Direct measurement against a reference standard

D.C. power

From 1 V to 1000 V and 0.1 A to 400 A (limited to 50 kW)

Active power

From 1 V to 750 V and 0.1 A to 100 A (limited to 50 kW) at Unity power -factor

Capability

with Calibration and Measurement Capability of -

DC power meters (up to 50 kW)
0.10% from 1 V to 1000 V and 0.1 A to < 1 A
0.05% from 1 V to 1000 V and 1 A to < 20 A
0.12% from 1 V to 1000 V and 20 A to < 100 A
0.22% from 1 V to 1000 V and 100 A to 400 A

Active power meters (Up to 50 kW, Unity Power Factor)
0.71% from 1 V to 1000 V and 0.1 A to < 1 A and 10 Hz to 5 kHz
0.60% from 1 V to 1000 V and 1 A to < 10 A and 10 Hz to 5 kHz
0.67% from 1 V to 1000 V and 10 A to < 20 A and 10 Hz to 5 kHz
 0.80% from 1 V to 1000 V and 20 A to 100 A and 10 Hz to 5 kHz

The only data displayed is that deemed relevant and necessary for the clear description of the activities and services covered by the scope of accreditation.

Grey text appearing in a SoA is additional freetext providing further refinement or information on the data in the preceding line entry.