National Association of Testing Authorities, Australia
Scope of Accreditation
Ausgrid
Site
Network Test
Accreditation No.
20351
Site No.
14568
Date of Accreditation
06 Feb 2001
Contact
Availability
Services conditionally available to external clients
Scope of Accreditation
ISO/IEC 17025 (2017)
Infrastructure and Asset Integrity
Service | Product | Determinant | Technique | Procedure | Limitations |
---|---|---|---|---|---|
Evaluation of high voltage/power equipment and components - Performance | Bushings; Insulators | Electrical resistance | AS 1265 | Excluding H.V. wet, RIV and switching impulse tests | |
Cable feeders; Cables | Electrical performance of cables and components | Voltage | AS 60060.1; AS 60840 | Applied direct voltage tests performed in the laboratory and the field Dielectric and sheath insulation | |
Electrical performance of cables and components | Insulation resistance | AS 60060.1 | Tests performed in the laboratory and the field applied voltages of up to 5000 V | ||
Electrical performance of cables and components | Voltage | AS 60060.1 | Applied alternating voltage tests performed in the laboratory and in the field Dielectric and sheath insulation | ||
Electrical performance of cables and components | Capacitance | AS 60840 | Tests performed in the laboratory and the field Tests up to 250 kV, 50 Hz | ||
Electrical performance of cables and components | Partial discharge | AS 60840 | Tests performed in the laboratory and the field Limited length samples at voltages up to 250 kV, 50 Hz | ||
Electrical performance of cables and components | Conductor resistance | AS 60840 | Tests performed in the laboratory and in the field | ||
Cable feeders; Cables; Overhead lines; Three phase cable installations | Electrical performance of cables and components | Sequence impedance | IEEE 1870 | Tests performed in the laboratory and the field | |
Clothing materials, gloves and tools for use in high voltage/power applications | Workplace electrical safety | Dielectric tests with alternating or direct voltages | AS 2225; AS 2978; AS 3527.2; ASTMD 120; AS 4202; ISSC 14 and ENA based methods | Tests on insulating boots, mats, gloves, sleeves, covers, sticks, tubes, rods | |
Electricity grid and industrial power supply equipment and systems | AC voltage | Not applicable | AS 60060.1 | ||
Loss tangent | Not applicable | AS 60060.1 | Tests performed in the laboratory and in the field Measurements up to 250 kV, 50 Hz; Measurement of dielectric dissipation factor at ambient temperature | ||
Capacitance | Not applicable | AS 60060.1 | Tests performed in the laboratory and in the field Capacitance measurements up to 250 kV, 50 Hz | ||
DC voltage | Not applicable | AS 60060.1 | Tests performed in the laboratory and in the field | ||
Partial discharge | Not applicable | AS 60270; IEC 60270 | Tests performed in the laboratory and in the field Measurement of discharge levels, inception and extinction voltages | ||
Insulated systems | Workplace electrical safety | Not applicable | ISSC 14; ASTM F478; F496; F479; F711; F712; F968 and IEC 60855 | Tests performed in the laboratory and the field Live line working equipment | |
Insulation products | Electric strength | Not applicable | IEC 60243 | Tests performed in the laboratory and the field At ambient temperature in the range up to 250 kV at 50 Hz | |
Loss tangent | Not applicable | ASTM D150 | Ambient temperature and up to 1 kV and at 50 Hz | ||
Insulation resistance | Not applicable | AS 1767.1; AS 1883 and IEC 60167 | Tests performed in the laboratory and the field Measurements at applied voltages up to 5000 V | ||
Relative permitivity | Not applicable | ASTM D924; IEC 60247 | 50 Hz and ambient temperature | ||
Insulation products; Insulators | DC voltage | Not applicable | AS 60060.1 | Tests performed in the laboratory and the field from -300 kV to 40 kV | |
Partial discharge | Not applicable | AS 60270 and IEC 60270 | Tests performed in the laboratory and in the field Measurement of discharge levels, inception and extinction voltages | ||
AC voltage | Not applicable | AS 60060.1 | Tests performed in the laboratory and the field Up to 250 kV at 50 Hz | ||
Oils | Electric strength | Not applicable | AS 1767.2.1; IEC 60156 and BS 1858 | Tests performed in the laboratory and the field Range 20 kV to 100 kV at 50 Hz | |
Platform access equipment for use in high voltage/power applications | Workplace electrical safety | Not applicable | AS 1418.10 | Tests performed in the laboratory and in the field Elevated working platforms for HV and LV services and accessories | |
Switching control and protective equipment for power systems | Dielectric dissipation; Electrical resistance; Insulation resistance; Partial discharge | Not applicable | AS 60265 | Tests performed in the laboratory and the field Tests on switches, switch-disconnectors, isolators, earthing switches, fuse switches, fuse circuit-breakers, switch gear and control gear | |
Applied high voltage withstand; Dielectric dissipation; Electrical resistance; Insulation resistance; Partial discharge | Not applicable | AS 2006; AS 62271-100; IEC 60056 | Tests performed in the laboratory and the field Circuit breakers and controllers | ||
Transformers and inductors | AC voltage; Applied high voltage withstand; Dielectric dissipation; Electric strength; Induced high voltage; Insulation resistance; Loss tangent; Overload; Overvoltage; Partial discharge; Power frequency withstand | Not applicable | AS 1243; AS 60044.2:2007; AS 60044.5:2004 | Tests performed in the laboratory and in the field Voltage transformers and protective voltage transformers 250 kV, 50 Hz (excluding H.V. wet and RIV tests); | |
AC voltage; Applied high voltage withstand; Dielectric dissipation; Electric strength; Insulation resistance; Loss tangent; Overload; Overvoltage; Partial discharge; Power frequency withstand | Not applicable | AS 60044.1:2007 | Tests performed in the laboratory and in the field Current transformers and protective current transformers 250 kV, 50 Hz excluding H.V. wet and RIV tests. | ||
AC voltage; Applied high voltage withstand; Dielectric dissipation; Electric strength; Induced high voltage; Insulation resistance; Loss tangent; Magnetising curves; Overload; Overvoltage; Partial discharge; Power frequency withstand; Winding resistance | Not applicable | AS 2374 | Tests performed in the laboratory and in the field Power transformers, earthing transformers and reactors up to 132 kV at 50 Hz |
The only data displayed is that deemed relevant and necessary for the clear description of the activities and services covered by the scope of accreditation.
Grey text appearing in a SoA is additional freetext providing further refinement or information on the data in the preceding line entry.
Accreditation No.
20351
Site No.
14568
Print date
26 Nov 2024