AusNet Transmission Group Pty Ltd

Site

Mondo – Electrical Testing Laboratory

Accreditation No.

754

Site No.

21190

Date of Accreditation

14 Feb 1969

Address

308 Hyde Street
Yarraville, VIC 3013
Australia

mondo.com.au

Contact

Mr Anthony Dyke P: +61 (03) 96881406

Availability

Services available to external clients

Scope of Accreditation

ISO/IEC 17025 (2017)

Infrastructure and Asset Integrity

Service Product Determinant Technique Procedure Limitations
Evaluation of high voltage/power equipment and components - Performance Cable feeders; Cables Partial discharge

AS 60270

DC voltage

AS 1931, IEC 60060-1, IEC 60060-2, IEC 60060-3 (field testing)

up to 60 kV DC and 50 mA

AC voltage

AS 1931, IEC 60060-1, IEC 60060-2, IEC 60060-3 (field testing)

up to 400 kV at 50 Hz and 700 mA

Insulation resistance

AusNet SMI 12-01-02, IEC 61442

up to 10 kV and 50 GΩ

Clothing materials, gloves and tools for use in high voltage/power applications Workplace electrical safety Insulation resistance

AS 2225, IEC 60903, ASTM D120, BS 697

Conducting materials, conductors and resistance alloys Conductivity; Resistance of length of conductor; Resistivity Not applicable

IEC 60468

Electricity grid and industrial power supply equipment and systems Partial discharge Not applicable

IEC 60270

DC voltage

AS 1931, IEC 60060-1, IEC 60060-2, IEC 60060-3 (field testing)


 

up to ± 60 kV, 50 mA

Impulse voltage

AS 1931, IEC 60060-1, IEC 60060-2

with positive polarity 1.2/50 μs waves up to 160 kV

Dielectric dissipation

AS 1931, IEC 60060-1, IEC 60060-2, IEC 60060-3 (field testing)

up to 400 kV

AC voltage

AS 1931, IEC 60060-1, IEC 60060-2, IEC 60060-3 (field testing)
 

up to 400 kV rms at 50 Hz

Insulated systems Workplace electrical safety Insulation resistance

AS 1418.10, AS 1931, IEC 60060-1, IEC 60060-2, IEC 60060-3 (field testing)

Workplace electrical safety Not applicable

AS 1977; AS 2978; 

ASTM D120; ASTM D149; ASTM D178; ASTM D1048; ASTM D1049; ASTM D1051; ASTM F478; ASTM F479; ASTM F968; 

IEC 60832

Insulation products; Insulators AC voltage Not applicable

AS 1931, IEC 60060-1, IEC 60060-2, IEC 60060-3 (field testing)

up to 400 kV and 700 mA

Surface and volume resistivity

IEC 62631-3-2

from 1 MΩ to 100 TΩ

DC voltage

AS 1931, IEC 60060-1, IEC 60060-2, IEC 60060-3 (field testing)

up to ±60 kV and 50 mA

Loss tangent

IEC 60250
 

from 50 Hz to 1 kHz

Partial discharge Not applicable

AS 60270, AS 60044.2, AS 60044.5, IEC 61869-3

Electric strength

IEC 60243, ASTM D149
 

up to 400 kV at 50 Hz and 700 mA

up to 60 kV dc and 50 mA

Impulse voltage

 AS 1931, IEC 60060-1,IEC 60060-2

 

from 1 kV to 160 kV (1.2 μs/50 μs)

Insulation resistance

IEC 60243, IEC 60167

Transformers and inductors Cut-off current characteristics

AS 1675, AS 60044.1, IEC 61869-2

field tests at 50 Hz on transformers with rated primary currents from 1 A to 5000 A
and rated secondary currents of 1 A and 5A

AC voltage

AS 1243, AS 60044.2, AS 60044.5, IEC 61869-3

field tests at 50 Hz on transformers with rated primary voltages up to 66 kV three phase
and 400 kV single phase, rated secondary voltages from 1 V to 1100 V